Customization: | Available |
---|---|
Nature of Source Flow: | DC/AC Power Supply |
Certification: | ISO9001, CE |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Device model | BNSX- 50KS |
BNSX- 100KS |
BNSX- 150KS |
BNSX- 250KS |
BNSX- 500KS |
BNSX- 500KTL |
BNSX- 630KTL |
Device power | 50kW | 100kW | 150kW | 250kW | 500kW | 500kW | 630kW |
DC side parameters | |||||||
DC voltage range | DC 0-800V | ||||||
AC side parameters (grid-connected) | |||||||
Rated voltage | AC 380V Three-phase five-wire system | AC 325/380V Three-phase five-wire system | |||||
Rated frequency | 50Hz | ||||||
Total current harmonic distortion | THD<4% | ||||||
Power factor | ≥0.99 | ||||||
AC side parameters (off-grid) | |||||||
Rated voltage | Line voltage AC 380V | ||||||
Rated frequency | 50Hz | ||||||
Rated current | 75A | 150A | 228A | 380A | 750A | 750A | 950A |
Output voltage distortion | <1%(Linear loads) | ||||||
Overload capacity | 120% 60s ,150% 10s | ||||||
Efficiency | |||||||
Max efficiency | 94.50% | ||||||
Protection features | |||||||
DC input protection | possess | ||||||
AC output protection | possess | ||||||
Overvoltage protection | possess | ||||||
Island protection | possess | ||||||
Overheat protection | possess | ||||||
Other | |||||||
Isolation method | Power frequency isolation | No isolation | |||||
User interface | LCD touch screen | ||||||
Communication interfaces | Ethernet / RS485 / CAN | ||||||
High/low voltage ride-through | possess | ||||||
Ingress protection | IP20 | ||||||
Operating temperature | - 20ºC ~ 45ºC | ||||||
Relative humidity | 0~95%(No condensation) | ||||||
Cooling method | Forced air cooling | ||||||
Working altitude | 2000m(More than 2000m derating) | ||||||
Size(W*D*H)(mm) | 800*650 *1900 | 1000*1000*1900 | 1800*1000 *1900 | 2200*1000 *2060 | 1600*1000*1900 |
1.Q:Are you manufacturers?